Design: The Series 900 Low Temperature Boiler is manufactured to exceed ASME Section IV standards and typically is used to provide supply temperatures from the coil of between 140-180°F, yet can accept exptremely low return temperatures (well below 100°F) without shocking the boiler. The temperature of the coil water is impacted by the temperature of the Space Heating side because the coil is immersed in that water.
These vessels contain 73 vertical firetubes, each of which is 1½” diameter, each fitted with a high-efficiency turbulator for maximum heat transfer. The combustion chamber is fully water-backed, with burners that are UL listed. The vessel capacity is 75 gallons with a heating surface of 78 sq. ft.
This boiler qualifies as a Category I gas appliance with industry standard controls wired to NEC specifications.
Safety: A well-made, heavy vessel is naturally a safer boiler. But TRIAD Boilers also have a firebox design that is completely backed by water, along with extra safety controls on the boiler that results in a very safe and secure package.
Standard Features: The following standard features include nationally known parts and controls that are available at most supply houses, allowing for quick and easy repair and maintenance, which can dramatically reduce down time:
- UL Listed Gas Trains and Control Systems.
- Choice of Power Burners.
- Main and Auxiliary Gas Valves
- Air Flow Switch
- Main Manual Leak Test Valve
- Bell and Gossett Circulating Pumps
- Honeywell Aquastat Relay
- Automatic Low Water Cutoff
- Honeywell Second High-Limit With Manual Reset.
- Burner Control Relay.
- High Visibility Operating Light.
- Pressure/Temperature Gauge
- Pressure Relief Valve
- 1½” Diameter Firetubes of SA178-A Steel
- Turbulators for Maximum Heat Transfer
- Two Inches of Insulation With a Painted Steel Jacket.
| Model | Input (BTU/Hr) | Gross OutPut | Combustion Efficiency | GPM @ Riseº F | Pressure Drop Thru the Coil |
| 600 | 600,000 | 508,800 | 85.0% | 20.3 @ 50º F | 2.86 |
| 700 | 700,000 | 589,400 | 84.0% | 23.6 @ 50º F | 3.53 |
| 800 | 800,000 | 664,800 | 83.0% | 26.7 @ 50º F | 4.53 |
| 900 | 900,000 | 746,100 | 83.0% | 29.8 @ 50º F | 5.65 |
| 1000 | 1,000,000 | N/A | N/A | N/A |
| Feature | Dimension |
| Vessel Width | 30.5" |
| Vessel Height | 66" |
| Boiler Weight | 1400 lbs |
| Boiler Depth w/ Burner | 61" |
| Gas Inlet Height | 12" |
| Return Water Inlet Height | 9" |
| Top of Vessel to Bottom Main | 9" |
| Height to Lower/Upper Coil Openings | 35.25"/56" |
| Height to Pump Flange | 38" |
| Height to Space Heater Return | 23.5" |
| Height Required at Installation | 90" |
| Clearance to Rear of Boiler | 18" |
| Clearance to Front of Boiler | 48" |
| Clearance to Side of Boiler | 18" |
| Clearance Between Boilers | 6" |
- Choice of burner manufacturers fired by natural gas, oil, propane, or combination fuel.
- Spark Ignition System for Combination Fuel Burners
- Low-High-Low firing
- CSD-1, IRI, FM
- Low-High Gas Train with Motorized Valves
- Fan-Damper relays
- Louver Box for Sealed Combustion Side-Wall Venting
- Barometric Dampers and Galvanized Tees
- Clean-out openings and plugs
- Microprocessor Control Panel for true lead-lag modulation
- Factory built and customized primary mains and headers
- Immersion Aquastats
- Various Relief Valve sizes for different applications
- Lifting Lugs
- Rail Legs




Product Details
Boiler Efficiencies